The FDUL221 line test device is a universal device for testing installed FDnet / C-NET fire alarm lines if no control center is yet connected. For troubleshooting for the electrician, installer or service technician.
Various functions can be accessed, e.g. B. Number of devices found, line errors found, location of the line error, short circuit, open circuit, ground fault with details of which conductor(s), scroll from detector to detector, with display of type and serial number, etc. Update the device software (firmware) via PC possible.

Powered by battery or via mains adapter.

Line test device including line connection set FDUL221-A and power supply set FDUL221-B.

Data sheet Sinteso -> 007228

Cerberus PRO -> A6V10203222

Operating voltage Min. DC 10 V, max. DC 30 V

Battery 2x 9V

Power adapter AC 240 V / DC 24 V, 624 mA

Power consumption Depending on the number of devices and display lighting

Operating temperature -25...+40 °C

Detector line voltage DC 32 V -> FDnet (FS20, AlgoRex)

DC 28 V -> FDnet (SIGMASYS)

DC 32 V -> C-NET (FS720)

Storage temperature -30...+75 °C
(-25...+60 °C with battery)

Relative humidity ≤95% rel. (no condensation)