To ensure that several branch lines do not fail in the event of a short circuit, line separators can be connected between them. The line separator is used where there are several stitches
be connected to the FDnet/C-NET at one point. The block can be connected to 2 separate loops
be connected. Converting existing collective systems to addressable Sinteso
and Cerberus PRO fire alarm systems. The block has a total of 9 line separators. Each line separator is an 'electronic switch' that is inserted into the FDnet/C-NET and switches off in the event of a short circuit
The negative conductor is separated so that the short-circuit-free side can continue to be operated. The line separator
has connections for the detector line, connections for the branch lines (T-branches), jumpers
Programming of the operating mode (1 or 2 loop), yellow LEDs for the status display signals this
Short circuit isolation.

Data sheet A6V10230308

Standard EN 54-17

Protection class IP30
with additional housing FDCH221 -> IP65

Operating voltage DC 12...33 V

Operating temperature -25...+70 °C

Storage temperature -30...+75 °C

Relative humidity ≤95% rel.

Communication protocol FDnet/C-NET

Communication protocol FDnet/C-NET

Quiescent current 2.25 mA (9x 250 μA) or
2x 1 mA (4x 250 μA)

System compatibility FDnet -> FS20, AlgoRex, SIGMASYS
C-NET -> FS720

Color ~RAL9010 pure white (housing)
Lid transparent, matt
~RAL9010 pure white (additional housing FDCH221)

Dimensions (W x H x D) 130 x 90 x 20 mm

Accessories hat mounting rail TS35_122
Hat mounting rail TS35_288
FDCH221 housing with cover, gasket and
screws
Metal cable gland M20 x 1.5
Metal lock nut M20
DBZ1190-AB connecting terminal 1.0...2.5 mm2
(3 pole)
FDCM291 mounting feet (25 pieces)