Skip to content

Produktübersicht

Signal base (acoustic, optical with red LED, speech)

The device is used to alert in an addressed fire alarm system and triggers an acoustic and visual danger signal with voice notification in the event of a fire alarm. The device is mounted on the ceiling, e.g. B. in hotel rooms, along escape routes, corridors, stairwells and offices.
The sound level, tones, light intensity and voice messages are adjustable and the alarm devices are synchronized. 15 languages ​​are integrated into the device; each voice message can be output in two different languages ​​one after the other.
The power supply is via FDnet/C-NET, no additional power is necessary. The device automatically monitors its visual and acoustic function.
The base must be ordered separately.

Technical data

default

EN 54-3; EN 54-23; EN 54-17

Protection class

IP21C; IP21C with deep base

Operating voltage

DC 16…33 V

operating temperatur

-25…70 °C

Operating current

5…29 mA (tone/voice and flash light activated)

Number of tones

16+2

Storage temperature

-30...+75 °C

Relative humidity

≤95% rel.

Quiescent current

400μA

Sound intensity

70…93 dB (A)

Light intensity

Bright = C-3-12
Medium = C-3-10
Weak = O-2.5-6.5
indicator

Cable size

0.2… 2.5mm2

Communication protocol

FDnet/C-NET

System compatibility

FDnet -> FS20 (MP7)
C-NET -> FS720 (IP7)

Dimensions (ø x H)

116x42.7mm

Color

Pure white, ∼RAL 9010

Accesories

FDB228 base (ceiling mount)
FDB229 deep base (ceiling mounting)
FDBZ298 cover plate
FDBZ221 additional ring
FDBZ291 Detector identifier
FDBZ293 Detector lock
LP720 detector lock
DBZ1190-AA micro clamp
DBZ1190-AB connection terminal

data sheet

A6V10725079