Skip to content

Produktübersicht

Input module (1 input)

For switching on 1 potential-free working or normally closed contact for reporting technical conditions (e.g. door or ventilation control) or for triggering alarms (e.g. sprinkler alarm).
1 input for potential-free signaling contacts. The input line is monitored for interruptions and short circuits (terminating resistors).
The input can be configured via the fire alarm control panel for status or alarm messages. Status display using LED. Power supply via FDnet/C-NET.
Input module including 2 resistors and 2 mounting feet for TS35 top-hat mounting rail.

Technical data

operating temperatur

-25…70 °C

default

EN 54-17; EN 54-18

Relative humidity

≤95% rel.

Protection class

IP30; IP65 with additional housing

Operating voltage

DC 12…33 V

Storage temperature

-30...+75 °C

Cable size

0.2... 1.5mm2 ( 2.5mm2 )

System compatibility

FDnet -> FS20
C-NET -> FS720

Communication protocol

FDnet/C-NET

Quiescent current

Max. 0.3mA

Dimensions (W x H x D)

95x71x23mm

Accesories

TS35_122 hat mounting rail; TS35_288 Hat mounting rail; FDCH221 housing IP65

data sheet

A6V10202196