Produktübersicht
Compact modular standard control center based on the MZ3 for RWA and ventilation
- Compact RWA standard control center based on the MZ3
- Features Preconfigured at the factory, meaning it can be used directly in the field
- With one RWA and two ventilation groups, depending on the size of the control center
- divided into 3 motor outputs
- Equipped as standard for activation by RWA control points, smoke detectors and BMA systems
- Connections for two ventilation buttons and a wind/rain detector
- If necessary, the two ventilation groups can be combined into one group by setting a bridge
- Energy supply tested according to EN 12101-10
Areas of application:
- Natural smoke extraction (NRA)
- Natural ventilation and ventilation
Technical data:
Mains supply voltage: 230 V AC/50 Hz (±15%)
System voltage: 27 V DC (nominal) (–25% /+10%)
Output current: 32 A
Input current: 5A
Power consumption: 1080W
Connection terminal push-in terminal max. 2.5 mm²
Battery fuse on site: 16 A
Battery: 2 x 12V/18Ah
Fuse: FKS 40 A
Voltage: 27 V DC (nominal) (-25% /+10%)
Power: (per motor channel) Pmax = 216 W, Pmin = 0 W
Rated current: (per motor channel) 8 A at ED 30, intrinsically safe
Opening/closing process: polarity reversal of the output voltage
Automatic activation: OPEN/CLOSE direction: after 3 minutes (in ventilation mode)
Line monitoring: via diodes
Number of motor channels: 3
Motor ducts/ventilation groups [1,2,3] | 3
Potential-free signaling contacts: tripping, fault, operation
RWA control point entrance: 1 RWA group, line monitored
Automatic detector input: line monitored
Input BMA: line-monitored normally open contact
Ventilation button input: Yes, 2 ventilation groups, can be combined into one
Wind/rain detector input: Yes
Dimensions (H x W x D): 800 x 600 x 210 mm
Nominal temperature: 20°C
Ambient temperature: -5°C to +40°C
Protection class: IP 42