Skip to content

Produktübersicht

Compact modular standard control center based on the MZ3 for RWA and ventilation

Advantages/features:
  • Compact RWA standard control center based on the MZ3
  • Features Preconfigured at the factory, meaning it can be used directly in the field
  • With one RWA and two ventilation groups, depending on the size of the control center
  • divided into 3 motor outputs
  • Equipped as standard for activation by RWA control points, smoke detectors and BMA systems
  • Connections for two ventilation buttons and a wind/rain detector
  • If necessary, the two ventilation groups can be combined into one group by setting a bridge
  • Energy supply tested according to EN 12101-10

Areas of application:

  • Natural smoke extraction (NRA)
  • Natural ventilation and ventilation

Technical data:

Mains supply voltage: 230 V AC/50 Hz (±15%)
System voltage: 27 V DC (nominal) (–25% /+10%)
Output current: 16 A
Input current: 2.5A
Power consumption: 540W
Connection terminal push-in terminal max. 2.5 mm²
Battery fuse on site: 16 A
Battery: 2 x 12V/12Ah
Fuse: FKS 40 A
Voltage: 27 V DC (nominal) (-25% /+10%)
Power: (per motor channel) Pmax = 216 W, Pmin = 0 W
Rated current: (per motor channel) 8 A at ED 30, intrinsically safe
Opening/closing process: polarity reversal of the output voltage
Automatic activation: OPEN/CLOSE direction: after 3 minutes (in ventilation mode)
Line monitoring: via diodes
Number of motor channels: 3
Motor ducts/ventilation groups [1,2] | 3
Potential-free signaling contacts: tripping, fault, operation
RWA control point entrance: 1 RWA group, line monitored
Automatic detector input: line monitored
Input BMA: line-monitored normally open contact
Ventilation button input: Yes, 2 ventilation groups, can be combined into one
Wind/rain detector input: Yes
Dimensions (H x W x D): 600 x 400 x 210 mm
Nominal temperature: 20°C
Ambient temperature: -5°C to +40°C
Protection class: IP 42