Skip to content

Produktübersicht

Thermal detector with differential and maximum response behavior for Loop 3000 for early fire detection and reporting in difficult environmental conditions, with two thermal sensors and bidirectional isolator according to EN 54-5 and EN 54-17

  • Thermal detector, approved according to EN 54-5 in temperature classes A1R, A1S (A1) and A2R, A2S (A2) and EN 54-17
  • Individual use of the detector as a maximum detector (static --> A1S, A2S) or as a differential detector with a maximum threshold (differential and static --> A1R, A2R) via the programmable and automatically adjustable detector sensitivities
  • Individual change of the detector class for sensitivity levels 2 to 4 using the Easy Check 3000
  • Periodically carrying out a sensor test
  • Automatic and manual addressing on Loop 3000
  • Integrated insulator and T-branch
  • Alarm output for controlling a parallel detector display
  • Functionalities fully integrated via Loop 3000 protocol
  • Presence and absence switching with selectable sensitivities
  • Storage of the last maintenance date
  • Multicolor LED for alarm (red) and fault display (yellow)
  • Delivery includes dust cover for installation phases

Technical data:

Supply voltage 15 V to 32 V DC (abs. max. 34 V DC) on 2-wire bus
Quiescent current 280µA
Alarm current 5mA
Exit OC: max. 10 mA for parallel display or piezo base
Ambient temperature -10°C to +60°C
humidity max. 95%
Protection class IP40
Weight approx. 80g
material SECTION
Color White housing (similar to RAL 9003)
Norms EN 54-5, EN 54-17
VdS recognition G203037
System approval S210001, S216001
CE CPR number 0786-CPR-20044
Dimensions (H x D) approx. 52 mm x 97 mm (with base)
Responsiveness Adjustable in 5 sensitivity levels