Skip to content

Produktübersicht

Control board for connecting up to 8 additional external outputs via changeover contacts to the fire alarm panels of the detect 3004plus series

  • Provision of additional 8 changeover contacts to control external circuits up to 250 V/5 A
  • 8 low-active inputs for parallel connection of the control board outputs
  • 1 input for enabling or blocking the function of the control card (e.g. for "BMZ door open")
  • 24 V power supply via the fire alarm control panel power supply
  • Module housing for easy installation on a top-hat rail
  • 8 LED displays for the status of the outputs

Technical data:

Supply voltage 21V to 28V DC
Quiescent current 5mA
Alarm current 30 mA to 240 mA (30 mA per relay)
Exit 8 changeover contacts 250 V/5 A
Ambient temperature -10°C to +50°C
humidity 10% to 85% (non-condensing)
Dimensions (H x W x D) 125mm x 110mm x 60mm
Weight 300g
material SECTION
Color green