Linear heat detector for early detection of a fire or overheating. It is particularly suitable for use in confined spaces or in harsh environmental conditions.

  • For use in garages, tunnels, parking garages, escalators, conveyor belts, cable ducts, cold storage, high-voltage, recycling systems, etc.
  • For connecting up to 300 m of sensor cable
  • Connection of the cables against mechanical, chemical and biological influences
  • Potential-free alarm and error output
  • Connection to the Loop 3000 via IOM 3311
  • Monitoring of wire breaks and short circuits

Technical data:

Supply voltage 24VDC
Alarm current 28mA
Exit potential-free relays,
2 x 30V/1A DC
Ambient temperature -25°C to +50°C
Protection class IP65
Dimensions (H x W x D) 110mm x 110mm x
66mm
Weight 270g
Norms 54-5; Cl. C
VdS recognition G203076
System approval S 210001, S 216001