Produktübersicht
3-channel infrared flame detector according to EN 54-10 for reliable detection of open flames.
Designed for use in harsh industrial environments such as warehouses for flammable liquids or gases and large high halls.
- 3-channel optics test for complete functional monitoring of the detector
- Function monitoring and evaluation of the measured values by microcontroller. Faults can be displayed on the detector or a separate line.
- High security against false alarms, caused for example by hot surfaces or strong sunlight
- Detection of an N-heptane fire measuring 33 cm x 33 cm from a distance of 25 meters
- Fast response time (1s to 30s)
- Different colored LED for status display of operation, fault and alarm
- Event memory
- Viewing angle 90°
- Connection via 1x IOM with the additionally available relay module item no. 32928
Technical data:
Supply voltage |
7.6V to 30V DC |
Quiescent current |
2.3mA |
Alarm current |
approx. 15 mA |
operating temperatur |
-20°C to +80°C |
Protection class |
IP67 |
Dimensions (H x W x D) |
92mm x 130mm x 140mm |
Weight |
990g |
material |
Housing: aluminum diecast |
Norms |
EN 54-10 |
VdS recognition |
G209141 |
System approval |
S210001, S216001 |
CE CPD number |
0786-CPD-20784 |
Remarks |
Accessories optional: Relay module Item no.: 32928 Cable recommendation JY (St) Y 2x2x0.8 mm², Conductor cross section max. 2.5 mm² |