Produktübersicht
Linear infrared smoke detector with automatic alignment using an infrared transmitter and receiver in one unit including a reflection prism. The Fireray 5000 requires 1 prism for a range of 8m to 50m and 4 prisms for a range of 50m to 100m
- Modular design
- Adaptation of the system to local conditions
- Automatic laser-assisted beam alignment can be activated or deactivated
- LCD display with optical menu navigation in the display for easy operation
- 2-wire interface between smoke detector and system controller
- The required fire sensitivity can be set using the fire threshold values in the range from 10% to 60%
- Connection to the Loop 3000 via IOM 3311
- Delay for fault and fire ranging from 2 to 30 seconds
- Automatic compensation for building movements
- Setting the delay times, separately for fire and fault
- The scope of delivery includes a detector head, a system control and a prism
Technical data:
Supply voltage |
14V to 28V DC |
Quiescent current |
8 to 12 mA |
Alarm current |
48 to 52 mA |
humidity |
max. 93% non-cond. |
Protection class |
IP54 |
Dimensions (H x W x D) |
135mm x 134mm x 134mm (Transmitter-receiver) |
Weight |
1.67kg |
material |
Housing: UL94V0 |
Norms |
54-12 |
VdS recognition |
G208017 |
System approval |
S 210001, S 216001 |
CE CPD number |
0832-CPD-0565 |
Remarks |
Accesories: Reflection prism (Item no. 32471) Manufacturer Fire fighting Enterprises Ltd. (Fireray 5000 Conventional) |