Skip to content

Produktübersicht

Manual call point for Loop 3000 for manually triggering an alarm with bidirectional isolator and status display via LED according to EN 54-11.

  • Push button mechanism to trigger a manual alarm
  • Triggered after the windshield is destroyed
  • Integrated reset mechanism
  • Automatic and manual addressing on Loop 3000
  • Integrated insulator and T-branch
  • Functionalities fully integrated via Loop 3000 protocol
  • Integrated red alarm LED

Technical data:

Supply voltage 15V to 32V DC
(abs. max. 34 V DC)
on 2-wire bus
Quiescent current 280µA
Alarm current 280µA; 5mA,
when alarm LED is active
Ambient temperature -10°C to +60°C
humidity max. 95%
Protection class IP42
Dimensions (H x W x D) 135mm x 135mm x
33mm
Weight 270g
material SECTION
Norms 54-11, 54-17
VdS recognition G203021
System approval S 210001, S 216001
CE CPD number 0786-CPD-20382
Remarks Accesories:
Replacement glass pane
Item No. 31910
Spare key
Item No. 40054