Intelligent input module for connecting a limit detector group to the Loop 3000 with bidirectional isolator according to EN 54-18. For connecting limit detectors in 12 or 24 V technology.

  • Selection of the detector group voltage via jumpers on the module board
  • External supply of the limit detector line for flexible use of various limit detectors with different current consumption and operating voltages
  • Short-circuit, wire break, pre-alarm and alarm thresholds can be parameterized
  • Automatic and manual addressing on Loop 3000
  • Integrated insulator and T-branch
  • Functionalities fully integrated via Loop 3000 protocol
  • Multicolor LED for alarm (red) and fault display (yellow)
  • Attractive, robust wall housing according to IP 54

Technical data:

Supply voltage 15V to 32V DC
(abs. max. 34 V DC)
on 2-wire bus
Quiescent current 560µA
Alarm current 560µA; 5 mA if
Alarm LED active
Ambient temperature -10°C to +60°C
humidity max. 95%
Protection class IP54
Dimensions (H x W x D) 93mm x 93mm x
55mm
Weight 190g
material SECTION
Color Housing light gray
(similar to RAL 7035)
Norms 54-17, 54-18
VdS recognition G206048
CE CPR number 0786-CPR-20373