Skip to content

Produktübersicht

Fire department display panel according to DIN 14662 for direct connection to the BMZ dc3500
via an RS485 interface without galvanic isolation. A connection to the detect 3004plus is also possible. An additional RS 232 module is required to connect to a detect 3004plus.
Initial information means for the fire brigade in accordance with DIN 14675 and EN 54-2.

  • Monitoring for short circuits and interruptions according to EN 54-2
  • Front door lock with box lock for profile half cylinder according to DIN 18252
  • Graphic display with 6 lines (128 x 64 pixels)
  • Operator/installer logo editable
  • RS-485 interface included in delivery
  • Configuration with the Prog4000 programming tool
  • Energy saving design
  • Reduction of environmental influences through capacitive buttons
  • History function
  • Standard version for surface mounting
  • Prepared for assembly and connection to the BMZ dc3500

Technical data:

Supply voltage 10V to 30V DC
Quiescent current approx. 30 mA/16 mA
(12V/24V)
Alarm current approx. 45 mA/23 mA
(12V/24V)
Dimensions (H x W x D) 185mm x 255mm x
58mm
Color RAL 7032 (pebble gray)
VdS recognition G213058