Skip to content

Detectomat fire alarm control panel detect 3004plus S housing, German

Original price €1.081,50 - Original price €1.081,50
Original price
€1.081,50
€1.081,50 - €1.081,50
Current price €1.081,50

Produktübersicht

Compact microprocessor-controlled fire alarm panel for connecting components from the Loop 3000 series.

  • Large, clear LC display
  • RS-232 interface for easy programming with DPT software
  • Space for 2 modules for connecting 126 loop participants from the Loop 3000 series per loop card
  • Programming of up to 128 detector groups
  • Event memory for up to 500 messages
  • Easy programming of up to 504 control links
  • Complies with EN 61000-6-3 Class B for radiation and is therefore suitable for use in sensitive areas
  • Connection option for limit value interfaces with the possibility of managing up to 16 detector groups using conventional technology
  • Possibility of connecting extinguishing valves of an extinguishing area in accordance with EN 12094 via extinguishing interface
  • Integrated slot for networking up to 63 components
  • Integrated interface of third-party extinguishing systems via standard extinguishing interface according to VdS
Supply voltage 230V AC (-15%/+10%)
Emergency power supply 2 x 12V/12Ah
Quiescent current 250mA
Alarm current 400mA
Exit 1 x 24 V/400 mA monitored for alarm. Up to 4 loops: 140 mA; 3500 m for max. 126 Loop 3000 elements; 3 relay outputs 250V/5 A for alarm and fault; 8 open collector outputs: 30V DC/90mA
Ambient temperature -5°C to +40°C
humidity 5% to 95% (non-condensing)
Protection class IP30
Dimensions (H x W x D) 490mm x 420mm x 150mm
Weight 12.5 kg without batteries
material sheet steel
Color light gray (similar to RAL 7035)
Norms 54-2, 54-4
VdS recognition G203068
System approval S210001
CE CPD number 0786-CPD-20817
further approvals EN 12094 for 1 area extinguishing systems
Remarks Scope of delivery without loop cards, networking modules, individual group display, fire brigade interface and accumulators. When using the integrated standard delete interface, an optional LED display board must be planned in the control panel front to ensure displays in accordance with EN 54-2.
Entrance 3 can be assigned for collective messages
Advertisement LC display 160 x 80 dots backlit
power adapter 24V DC/72W/3.5A; 1 output: 24 V DC/800 mA for external consumers
Interfaces RS-232, Bitbus (RS-485 based), fire brigade interface