Intelligent input/output module for the Loop 3000 for controlling external optical and acoustic signaling devices with bidirectional isolator according to EN 54-18. With a monitored fault input and a potential-free relay output for signaling devices.

  • Integrated automatic reset function of the output when the fire alarm control panel signals “external signaling devices on/off”.
  • Connection module with a freely programmable fault input and an output preassigned for connecting signal generators
  • Monitoring the operating status via the Loop 3000
  • Independent programming of input and output
  • Automatic and manual addressing on Loop 3000
  • Integrated insulator and T-branch
  • Functionalities fully integrated via Loop 3000 protocol
  • Multicolor LED for alarm (red) and fault display (yellow)
  • Programming option for different switching variants of the input and output, also with time control
  • Robust wall housing according to IP 54


Supply voltage 15 V to 32 V DC (abs. max. 34 V DC) on 2-wire bus
Quiescent current 460µA
Alarm current 460µA; 5 mA with activated LED
Exit 1 relay 1 changeover contact 30 V DC/1 A
Ambient temperature -10°C to +60°C
humidity max. 95%
Protection class IP54
Dimensions (H x W x D) 93mm x 93mm x 55mm
Weight 185g
material SECTION
Color White housing
Norms DIN EN 54-18, EN 54-17
VdS recognition G205029
System approval S210001, S216001
CE CPR number 0786-CPR-20459
Remarks Accessories:<br>A monitored output can be implemented with the UBW 3311 1A (Art. No. 33542).