Skip to content

Produktübersicht

Application: Ventilation, RWA, ferralux®-NRWG

Options
Thrust tube end with thread for fork head
Rear suspension eyebolt/clevis

S3
Integrated night cycle safe load switching electronics S3

Options
Programming run-monitored multiple operation (up to s 300 mm)
Programming sequence control with locking drives (S3 / S12)

S12
Integrated intelligent control electronics S12

Options
Programming synchronous operation of max. 4 drives and special functions
M-COM for automatic configuration of synchronous operation and sequence controls
Locking drives (S3 / S12) in drive network systems

TECHNICAL DATA
UN rated voltage 24V DC (19 V ... 28 V)
IN rated current 0.8 A
IA shutdown current 1.0 A
PN rated consumption 19 W
DC duty cycle 5 cycles (ED 30% - ON: 3 min. / OFF: 7 min.)
Protection class IP 65
Ambient temperature -5 °C ... +60 °C
FZ tensile force max. 1000 N
FH locking force 5000 N (depending on fastening)
Push tube stainless steel
Connection cable halogen-free, gray 3 x 1.0 mm², ~ 3 m
v Speed ​​4.6 mm/s 4.6 mm/s
s stroke 100 – 1200 mm
L total length S3: s + 302 mm
S12: s + 342mm
(see order details)
Emission sound pressure level 70 dB (A)