Application: For controlling intelligent AUMÜLLER S12 / S3 drives up to a maximum of 10 A total current.

TECHNICAL DATA (rated values)
Operating voltage: 24V DC
Output voltage: 24 V DC (20 – 28 V DC / 0.5 Vpp)
Own consumption: 6 mA
Output current: 10A
Housing (WxHxD): 100 x 120 x 22.5 mm, ABS, black
Module units: 1 ME
Inputs: ventilation button (max. 10 pieces), feedback contact OPEN/CLOSE,
0 - 10 V analog input
Outputs: drive line (AUMÜLLER S12 / S3)
Displays: operation, malfunction, EMERGENCY OPEN, direction OPEN / CLOSE
Controls: Front button: OPEN / CLOSE
Connections: plug-in terminals 1 mm² rigid, drives: 2.5 mm²,
Flat connector 6.3 mm; power supply,
Socket and plug with cable for internal BUS
0-10V analog input

Features: Monitored drive cable, fastening on 35 mm top-hat rail,
Parameterization of functional and performance features that deviate from the standard