Skip to content

Produktübersicht

Application: Smoke and heat extraction center in compact design for stairwells, for controlling electromotive RWA and
Ventilation drives with operating voltage 24 V DC.

TECHNICAL DATA (rated values)
Operating voltage: 230 V AC (195 – 253 V AC, 50/60 Hz)
Max. power consumption: 115 W
Output voltage: 24 V DC (20 – 28 V DC / 2 Vpp)
Output current: 2.5A
Ambient temperature: -5°C … + 40°C
Protection class: IP30
Housing: AP, sheet steel, RAL 7035 (light gray)
Dimensions (WxHxD): 225 x 285 x 122 mm
Connection terminals: 1.5 mm² / drives: 4 mm² (rigid)
VdS recognition number: G 514001 (without HSE button or with orange HSE button)
Base board: 1 RWA group / 1 ventilation group

Feature/equipment
Further setting options (such as maintenance period) with a paid software license
Cable feed from above / below / behind
Optional housing for flush mounting
Prepared for 2 maintenance-free emergency power batteries 2x 12 V / 2.3 Ah (order no. 541000)
Version with HSE and ventilation button on the housing cover