Application: Plug-in card for communication between the Aumüller controls LZ1, LZ6 and EMB 7300 with the KNX BUS system.

TECHNICAL DATA (rated values)
Operating voltage: 24V DC
Ambient temperature: -5°C … + 40°C
Relative humidity: (not condensate) 5% … 90%
Data points: up to 16 pieces per motor line
BUS current: 9mA
Housing: without (assembled circuit board)
Dimensions (WxH): 51 x 42 mm
Connection terminals: 2 x 2 x 0.8 mm (KNX BUS terminal)

Feature/equipment
Data from the control (e.g. drive position) is sent to the KNX BUS.
The controls receive direct commands from the KNX BUS (e.g. position data, weather data).
The licensed version of the EMB compact configurator is required for commissioning.