Skip to content

Produktübersicht

Technical description:
Optical smoke switch with smoke detection based on the scattered light principle
(EN 54, Part 7). An additional one
Temperature sensor speaks to you
Temperature limit of approx. + 70 °C.
The evaluation electronics monitors the
Smoke measuring part for contamination and
Disturbance. The respective operating states
are displayed visually. One yourself
regulating alarm threshold tracking ensures
for consistent response. The integrated termination module can be connected via a magnet in the base
be activated if the evaluation unit has line monitoring
supports. For different
Various mounting bases are available for mounting variants. Building supervision
approved for the area of ​​application
Hold-open systems. (Mounting base is
not included)
Performance features:
- Optical smoke detection after
Scattered light principle
- No use of radioactive ones
preparations
- Visual display for operation, lightweight
dirty, heavily dirty,
Disturbance and alarm
- Integrated final module
- Potential-free contact, opens when
Alarm and disturbance
- Measuring chamber monitoring
- Standard installation, cable without
Functional maintenance
- RS bus compatible
- Building authority approved by DIBt
- available similar to the colors of the
RAL Classic color palette
Nominal data:
Operating voltage 18 to 28 V DC
Current consumption max. 25 mA
Switching capacity relay 30 V / 1 A
Protection class IP 42
Smoke detection according to EN 54, part 7
Trigger temperature approx. + 70 °C
Operating ambient temperature
-30°C to +60°C
Dimensions DxH 80x33 mm without base
Weight 120g
Manufacturer: Hekatron Vertriebs GmbH
Type: ORS 142