Skip to content

Hekatron ventilation smoke switch system

Original price €442,68 - Original price €442,68
Original price
€442,68
€442,68 - €442,68
Current price €442,68

Produktübersicht

Technical description:
Ventilation smoke switch system for smoke monitoring in ventilation ducts.
The system is assembled by
Outside. The structure can be done on channels
round and square cross sections
take place.
The built-in rectifier board
allows the connection of 24 V
DC and AC voltage.
The alarm relay of the optical smoke switch is with alarm storage
fitted. Resetting one
Alarm is only possible if there is no smoke
and is carried out by pressing the reset button in the device or by interrupting the power supply. The
Evaluation electronics monitor the smoke measuring part for contamination and malfunctions.
The operating states operation,
Pollution, disruption and alarm become
visually displayed and are from the outside
visible. Through the automatic alarm threshold tracking and the
intelligent evaluation electronics is one
consistent response and
thus a safe operation and a
increased service life guaranteed.
Thanks to the maintenance-friendly structure
The annual revision can be carried out without tools
take place.
Performance features:
- Operation with 24 V direct and alternating current
voltage possible
- Comfort connection terminal strip with
Reset button
- For channels with round and square ones
Cross sections
- Easy removal of the inlet pipe
maintenance
- Inlet pipe can be optimally adjusted in length
- Can be used up to 20 m/second
- Optical smoke detection after
Scattered light principle
- No use of radioactive ones
preparations
- Visual display for operation,
Dirty, fault and alarm from
visible from the outside
- Potential-free contact, opens when
Alarm and disturbance
- Alarm storage
- Measuring chamber monitoring
- Standard installation, cable without
Functional maintenance
- RS bus compatible
- VdS no.: G 207084
- Yearly maintenance
- 5 year guarantee
- The LRS guarantee conditions apply
(www.hekatron.de)
Nominal data housing:
Protection class on channel IP 54
Cable entry 4x Ø 6-10 mm
Duct installation depth 140 to 345 mm
Air flow 1 to 20 m/second
Dimensions HxWxD
without inlet and outlet pipe 100x135x247 mm
Weight max. 460 g
Material PC / anodized aluminum tube
Color blue, lid transparent
Rated smoke switch/rectifier data:
Operating voltage 24 V AC/DC
Current consumption max. 22 mA
Switching capacity relay 30 V DC / 1 A
Relative humidity up to 95% without
dew
Smoke detection according to EN 54, part 7
Operating ambient temperature
-20°C to +60°C
Weight 120g
Manufacturer: Hekatron Vertriebs GmbH
Type: LRS 02 24V AC/DC