Produktübersicht
Compact microprocessor-controlled fire alarm panel for connecting components from the Loop 3000 series
- Clear display and easy operation, color display with touchscreen
- USB interface for easy programming with DPT software
- Space for up to 15 modules for connecting up to 126 loop participants from the Loop 3000 series per loop card
- Programming of up to 1890 detector groups
- Event memory for up to 100,000 messages
- Easy programming of up to 10,000 control links
Supply voltage | 90-265V; 50-60Hz |
---|---|
Emergency power supply | 2 x 12V/17Ah, 26Ah, 45Ah |
Quiescent current | 280mA |
Alarm current | min. 360 mA depending on expansion |
Exit | 1 x 24 V/800 mA monitored for alarm. 2 relay outputs for alarm and fault, 4 relay outputs freely programmable (each 30 V 2 A DC / 125 V 0.5 A AC) |
Ambient temperature | -5°C to +40°C |
humidity | 5% to 95% (non-condensing) |
Protection class | IP30 |
Dimensions (H x W x D) | 600mm x 450mm x 240mm |
Weight | 17.7 kg (without batteries) |
material | sheet steel |
Color | RAL 9006 |
Norms | EN 54-2: 1997 A1: 2006; EN 54-4: 1997 A2: 2006 |
VdS recognition | G-214222 |
CE CPR number | 0786-CPR-21428 |
Remarks | The standard includes a license for up to 250 participants. |
Entrance | 2 potential-free programmable inputs |
Advertisement | 24-bit color display 480 x 272 dots, LED backlight. 18 permanent status lights |
power adapter | Pmax: 166W |
Interfaces | USB slave |
You may also like
Detectomat fire alarm panel dc3500 SL, deep housing
DetectomatCompact microprocessor-controlled fire alarm panel for connecting components from the Loop 3000 series Clear display and easy operatio...
View full detailsDetectomat Brandmelderzentrale DC3500 SE max. 100 Teilnehmer
DetectomatDie Brandmelderzentrale DC3500 SE (Art.-Nr. 33087) ist eine kompakte, mikroprozessorgesteuerte Brandmelderzentrale für bis zu 100 Loopteilnehmer de...
View full detailsDetectomat input/output module, 2-fold
DetectomatIntelligent input/output module for the Loop 3000 with bidirectional isolator according to EN 54-18 and EN 54-17. With two monitored inputs and two...
View full detailsDetectomat limit value module
DetectomatIntelligent input module for connecting a limit detector group to the Loop 3000 with bidirectional isolator according to EN 54-18. For connecting ...
View full detailsDetectomat input/output module 1 compartment
DetectomatIntelligent input/output module for the Loop 3000 with bidirectional isolator according to EN 54-18 and EN 54-17. With a monitored input and a p...
View full details