Technical description:
Gas sensor for wall mounting in the
Ex areas in zones 1 and 2. Der
Sensor detects explosive gases
and vapors and works according to the principle
the heat tone. All electronics
is housed in the measuring sensor. For the
Connection to the evaluation device
only three conductors are required.
Performance features:
- Detects explosive gases and
fumes
- Measuring range 0 to 100% LEL
- ATEX approved
- Use in Ex areas Zones 1 and 2
- Digital implementation in one
proportional measuring current (4-20 mA)
- One-man calibration
- Programmable and parameterizable
Zones 1 and 2 via optional
Control device
- Connection with 3-wire technology
Nominal data:
Area of ​​application Ex areas
Zones 1 and 2
Protection class IP 54
Cable length up to 1000 m
Explosion protection type
Electronics EEx de [ib] IIC T6
Sensor EEx d IIC T6
Operating ambient temperature
-20°C to +55°C
Relative humidity 30% to 90%
Dimensions HxWxD 170x110x85 mm
Manufacturer: Hekatron Vertriebs GmbH
Type: HC 100MH