Produktübersicht
Technical description:
Optical smoke switch combined with
a short-circuit-proof power supply and triggering device to form a compact smoke control center. Smoke switch with alarm threshold tracking and contamination indicator. There is one for tax tasks
Potential changeover contact for
Disposal. The separate upper housing parts are in the versions
Standard and design available.
Approved by building authorities for
Area of application for hold-open systems.
Performance features:
- Visual display for operation, lightweight
dirty, heavily dirty,
Disturbance and alarm
- Alarm threshold tracking and
Temperature sensor
- Measuring chamber monitoring
- RS bus compatible
- Optical smoke detection after
Scattered light principle
- No use of radioactive ones
preparations
- 1 changeover contact, with 24 V DC
full of potential
- Short circuit proof
- Thermal protection
- Rated input voltage 230 V AC
- Rated output voltage 24 V DC
- Output current up to 440 mA
- Building authority approved by DIBt
Nominal data:
- Rated input voltage 230 V AC
- Rated output voltage 24 V DC
- Output current max. 440 mA
- Switching capacity relay 30 V AC/DC / 1 A
- Protection class IP 20
- Operating ambient temperature
+5°C to +40°C
- Smoke detection according to EN 54/7
- Temperature switch-off at approx. 70 °C
- Dim. HxWxD without top
31.5x246x33mm
- Surface-mounted lintel installation
Manufacturer: Hekatron Vertriebs GmbH
Type: RSZ 142