The air sample smoke detection set is a passive monitoring system without its own fan. It uses
the pressure differences in the ventilation system in order to continuously take air samples via the air flow pipe
removed from the ventilation duct and fed into the air sample smoke detector set.
The air sample smoke detector kit only works when the ventilation system is in operation and the air
circulates.
The air to be monitored must normally be clean, ie free of dust and aerosols.
If the smoke detector detects a certain concentration of smoke, the corresponding danger level is reported to the fire alarm control panel, which in turn triggers an alarm.
The specialized Sinteso and Cerberus™ PRO detectors and bases must be ordered separately.

Data sheet A6V10405166

Protection class IP54

Relative humidity ≤95% rel.

Operating temperature -20…+50 °C

System compatibility Sinteso: FDnet, collective

Cerberus PRO: C-NET, collective

Permissible air speed 1…20 m/s

Air flow indicator ≥1 m/s

Color ~RAL 7001, silver gray

Accessories FDBZ290-AA Air flow tube, length 600 mm
FDBZ290-AB air flow tube, length 1500 mm
FDBZ290-AC air flow tube, length 2800 mm
FDBZ290-AD mounting device
FDBZ292-AD seal set