Skip to content

Produktübersicht

Zone module, external power supply, C-NET.
- Connection of a detector line (collective or conventional 110 series, DS11, SynoLINE 300/600).
the C-NET
- LED display of the status of the detector line: fault, test, etc.
- Two-wire installation for all cable types
- DC 24 V external power supply (detector lines galvanically isolated)
- Microprocessor-controlled signal evaluation
- Communication via C-NET (individually addressed)
- Can be used in dry, dusty and damp areas
- Various mounting options
- Group module including 1 20 V voltage reference diode and 2 mounting feet for TS35 top hat rail

Data sheet A6V10402143

Operating temperature -10…+50 °C

Standard EN 54-17, EN 54-18

Relative humidity ≤95% rel.

Protection class IP30

IP65: with additional housing FDCH221

Operating voltage DC 12...33 V

Terminating resistor 20 V transzorb diode or EOL22(Ex)

Storage temperature -30…+70 °C

Cable size 0.2...1.5 mm2

System compatibility C-NET > FS720

C-NET communication protocol

Detector line 110 series / DS11, SynoLINE300/600

Dimensions (W x H x D) 95 x 71 x 23 mm

Color of housing: ~RAL 9010 pure white

Lid: Transparent matt

Input voltage DC 12...33 V

Accessories FDCH221 housing with cover, seal and
screws
A5Q00004478 Metal cable gland M20 x
1.5
A5Q00004479 Metal lock nut M20
DBZ1190-AB connecting terminal 1.0…2.5 mm2
(3 pole)
FDCM291 mounting feet (25 pieces)