Produktübersicht
Optical smoke detector for Loop 3000 for early fire detection and notification, with two optical sensors and bidirectional isolator according to EN 54-7 and EN 54-17
- Contamination detection through additional, independent measuring section
- Detector sensitivities are both automatically adjustable and programmable
- Fault monitoring for measuring chamber signal and Loop 3000 electronics
- Periodically carrying out a sensor test
- Automatic and manual addressing on Loop 3000
- Integrated insulator and T-branch
- Alarm output for controlling a parallel detector display
- Functionalities fully integrated via Loop 3000 protocol
- Presence and absence switching with selectable sensitivities
- Storage of the last maintenance date
- Multicolor LED for alarm (red) and fault display (yellow)
- Delivery includes dust cover for installation phases
Technical data:
| Supply voltage |
15 V to 32 V DC (abs. max. 34 V DC) on 2-wire bus |
| Quiescent current |
280µA |
| Alarm current |
5mA |
| Exit |
OC: max. 10 mA for parallel display or piezo base |
| Ambient temperature |
-10°C to +60°C |
| humidity |
max. 95% |
| Protection class |
IP40 |
| Weight |
approx. 80g |
| material |
SECTION |
| Color |
White housing (similar to RAL 9003) |
| Norms |
EN 54-7, EN 54-17 |
| VdS recognition |
G 202002 |
| System approval |
S 210001, S 216001 |
| CE CPD number |
0786-CPD-20035 |
| Dimensions (H x D) |
approx. 44 mm x 97 mm (with base) |
| Responsiveness |
Adjustable in 5 sensitivity levels |