Produktübersicht
Fire brigade information and operating system with FAT4000 and FBF4000
Initial information means for the fire brigade in accordance with DIN 14675 and EN 54-2
Redundant connection to the BMZ in conjunction with the ADP4000 adapter. The ADP 4000 adapter is not included in the scope of delivery and must be ordered separately.
For a non-redundant connection, an additional RS 485 module (32939) must be ordered. An RS 485 interface is already pre-installed on the fire department module. With the dc3500, no ADP4000 is required for the non-redundant connection.
Connection of the components in a loop structure.
- Supply voltage and signal path redundant
- Monitoring for short circuits and interruptions according to EN 54-2
- Monitoring of transmission paths according to EN 54-13
- Full functionality in the event of a disruption to a line route
- Graphic display with 6 lines (128 x 64 pixels)
- Operator/installer logo editable
- Free slot for additional interface for expansion
- Configuration with the Prog4000 programming tool
- Energy saving design
- Reduction of environmental influences through capacitive buttons
- History function
- Front door lock with box lock for profile half cylinder according to DIN 18252
- Standard version for surface mounting, single-leaf sheet steel housing
- Optimized accessibility for installation and assembly, swing frame
- Prepared for assembly and connection to the BMZ dc3500
Technical data:
Supply voltage |
10V to 30V DC |
Dimensions (H x W x D) |
380mm x 255mm x 60mm |
Color |
RAL 3000 (fire red) |
VdS recognition |
G213057 |