Skip to content

Detectomat multiple sensor detector CO

Original price €339,29 - Original price €339,29
Original price
€339,29
€339,29 - €339,29
Current price €339,29

Produktübersicht

Intelligent multiple sensor detector for Loop 3000 for early fire detection and reporting in difficult environmental conditions. With a sensor system for measuring carbon monoxide combined with two thermal sensors and a bidirectional isolator in accordance with EN 54-5 and EN 54-17 for the earliest detection of all types of smoldering fires, such as: B. for monitoring cable shafts and sawmills. The PL 3300 COBT continuously monitors the measured variables temperature and CO concentration during normal operation.

  • Alarm evaluation with professional CO sensors
  • Independent measurement of carbon monoxide with 2 alarm thresholds: pre-alarm: 15 ppm in 15 min, alarm: 30 ppm in 60 min.
  • Integrated acoustics for CO pre-alarm and CO alarm
  • Highest operational reliability through intelligent linking: thermal and CO sensor via algorithms
  • Integrated heat measurement as a differential method and maximum value according to EN 54-5 1A
  • Periodically carrying out a sensor test
  • Automatic and manual addressing on Loop 3000
  • Integrated insulator and T-branch
  • Alarm output for controlling a parallel detector display
  • Functionalities fully integrated via Loop 3000 protocol
  • Presence and absence switching
  • Illustration of a temperature profile of the fire alarm system
  • Multi-color LED for alarm (red) and fault indication (yellow)

Technical data:

Supply voltage 15V to 32V DC
(abs. max. 34 V DC)
on 2-wire bus
Quiescent current 600µA
Alarm current 5mA
Exit OC: max. 10mA
for parallel display
or piezo base
Ambient temperature -10°C to +60°C
humidity max. 95%
Protection class IP40
material SECTION
Color White housing
(similar to RAL 9003)
Norms 54-5, 54-17 Class 1A
VdS recognition G207005
System approval S 210001, S 216001
CE CPD number 0786-CPD-20582
CE CPR number 0786-CPR-20582
Remarks Further information
for operation, maintenance
and exchange
Refer to the operating instructions
51481.
Dimensions (H x D) 52mm x 100mm
Responsiveness CO alarm: at 30 ppm,
Heat EN 54-5 1A