Produktübersicht
Connection box for alarm lines
- Compact connection box for supplying and controlling alarm and evacuation devices within a fire compartment
- The basic version consists of a housing with a switching power supply and a module kit for monitored control of an alarm line
- The control of up to 4 alarm lines can be integrated into the device using a maximum of three expansion kits (item no. 33083).
- The supply unit combines the functions of energy supply and battery charging device
- The primary-switched switching power supply has an electronic overload function and integrated deep discharge protection
- Accumulators from 2-19Ah can be used to bridge the 24V output voltage
- The up to 4 output modules that can be integrated have an integrated isolator according to EN 54-18 and a reset function. It is attached to the housing using a simple top-hat rail installation
- Each output module monitors the output line for wire breaks and short circuits
- The connection to the Loop 3000 provides full programming and setting options
Supply voltage |
Mains: 230V AC/50 Hz <br>Loop 3000: 15 to 32V DC (abs. max. 34V DC) |
Ambient temperature |
-5°C to +40°C |
humidity |
max. 95% (non-condensing) |
Protection class |
IP30 |
Dimensions (H x W x D) |
404mm x 404mm x 110mm |
Weight |
5kg without batteries |
material |
Metal (housing and door) |
Color |
Light gray with surface structure, according to RAL 7035 |
Norms |
Power supply EN 54-4, output module EN54-17, 18 |
Remarks |
Basic EVAC box with 1 OMS (bridging time 72h rest and 30min alarm) 7.2Ah (Item no.: 40056) (Item no. <br>Basic EVAC box with 2-4 OMS using expansion kit (Item. -No. 33083) (bridging time 72h rest and 30min alarm) 12Ah (item no. 30155) Batteries are not included in delivery |
Output voltage |
24VDC |
Output current |
1.5A according to operating mode <br>(1A for signaling and 0.5A for battery charging) |