Skip to content

Detectomat Alarmline II - Linear heat detector, PC programmable

Original price €2.397,43 - Original price €2.397,43
Original price
€2.397,43
€2.397,43 - €2.397,43
Current price €2.397,43

Produktübersicht

The analogue, line-shaped heat detection system Alarmline II is a flexible, long-lasting form of fire detection, suitable for use in confined spaces or harsh environmental conditions. The system consists of an evaluation unit that is PC-programmable and a sensor cable. The Alarmline II sensor cable is a four-conductor cable that senses temperature changes by continuously monitoring the resistance of the specially doped polymer insulation (NTC). An abnormal change in resistance along the sensor cable triggers either pre-alarm or alarm conditions in the evaluation unit. The Alarmline II evaluation unit ensures the monitoring of the Alarmline II sensor cable, the configuration of alarm and pre-alarm temperatures as well as the interfaces to the BMZ.

  • For use in tunnels, parking garages, escalators, conveyor belts, cold storage, high-voltage and recycling systems, among others
  • The pre-alarm and alarm temperatures are programmed using a laptop on which the programming software is installed
  • Potential-free changeover contacts for pre-alarm and alarm, opto-isolated phototransistor as fault output
  • Display alarm / pre-alarm red LED
  • Yellow LED malfunction display
  • Green LED power supply indicator
  • Remote reset possible
  • With cable break and short circuit monitoring
  • Combined Max/Diff detector adjustable to response classes A1, A2, B, C and freely adjustable
  • For connecting up to 500m of sensor cable
  • Detects temperature excesses even over long distances
  • Resistant to mechanical and chemical influences, corrosion, moisture, dust
  • Chassis temperature alarm
  • Connection to the Loop 3000 via IOM3311, see connection diagram 56567
  • Termination unit for closing the end of the sensor cable is included
Supply voltage 20V - 28V DC
Quiescent current <70mA
Alarm current <80mA
Exit Pre-alarm/alarm: (changeover contact) 2A at 30V DC; Malfunction: Opto-isolated phototransistor max. 50V at 20mA
operating temperatur 0°C - 50°C
humidity 0% - 95 RH (ma 75% RH if < 75m cable and 54°C alarm temperature)
Protection class IP65
Dimensions (H x W x D) 180x182x90mm
Weight 804g
material Polycarbonate
Color Light gray
Norms EN 54-22
VdS recognition G220035
further approvals UL 521
Remarks Manufacturer: Kidde Deutschland GmbH
Entrance External Reset: Isolated input for remote module reset (20 - 28V DC pulse for min. 5 sec.)