Produktübersicht
Input module (1 input)
For switching on 1 potential-free working or normally closed contact for reporting technical conditions (e.g. door or ventilation control) or for triggering alarms (e.g. sprinkler alarm).
1 input for potential-free signaling contacts. The input line is monitored for interruptions and short circuits (terminating resistors).
The input can be configured via the fire alarm control panel for status or alarm messages. Status display using LED. Power supply via FDnet/C-NET.
Input module including 2 resistors and 2 mounting feet for TS35 top-hat mounting rail.
operating temperatur |
-25…70 °C |
default |
EN 54-17; EN 54-18 |
Relative humidity |
≤95% rel. |
Protection class |
IP30; IP65 with additional housing |
Operating voltage |
DC 12…33 V |
Storage temperature |
-30...+75 °C |
Cable size |
0.2... 1.5mm2 ( 2.5mm2 ) |
System compatibility |
FDnet -> FS20 |
Communication protocol |
FDnet/C-NET |
Quiescent current |
Max. 0.3mA |
Dimensions (W x H x D) |
95x71x23mm |
Accesories |
TS35_122 hat mounting rail; TS35_288 Hat mounting rail; FDCH221 housing IP65 |
data sheet |
A6V10202196 |