Produktübersicht
Heat differential maximum detector with limit value technology for Ex Zone 1. Designed for use in areas where rapid heat development due to flames is to be expected. Robust heat detector with 2 temperature sensors also for use in industrial areas. Heat detector with intrinsically safe electronics for operation in potentially explosive areas. Connection to the BMZ via the TCM and a Zener barrier (item no.: 33084). The barrier must be installed according to the manufacturer's instructions and outside of the Ex area.
- Adaptation to ambient conditions through 2 temperature sensors
- Combined differential and maximum evaluation of temperature increases
- Detection principle: NTC temperature sensor
- Alarm is indicated by 1 red LED
- Temperature class, differential measurement: Class C, according to EN 54-5:2000 / A1:2002
- Static trigger temperature: 84°C to 100°C
- Number of detectors per line max. 10
- Connection/assembly see connection diagram 56543
Technical data:
Supply voltage |
7.6V - 13.2V DC |
Quiescent current |
approx. 0.07 mA |
Alarm current |
approx. 15 mA |
operating temperatur |
-20°C to +80°C |
humidity |
max. 95% No condensation |
Protection class |
IP 23, when using the choke plugs and sealing the mounting holes |
Weight |
140g |
material |
Polycarbonate |
Norms |
EN 54-5 |
VdS recognition |
G27918 |
CE CPD number |
0786-CPD-20209 |
further approvals |
Ex conformity according to 94/9/EC Ex II 2G Ex ib IIC T6…T4 b Ex conformity Russia according to TP TC 012/2011: 1Ex ib IIC T5/T4 Gb |
Remarks |
The detector housing has a high surface resistance. Electrostatic charging must be avoided. Electrostatic shielding is recommended. The corresponding detector base is not included in the scope of delivery and is available under item number 33043. |
Dimensions (H x D) |
68mm x 113mm |
Color casing |
white |
ATEX number |
Type test certificate: BVS 03 ATEX E 104 |