Intelligent optical smoke detector for Loop 3000 specifically for direct use in ventilation ducts and smoke extraction systems, with two optical sensors and bidirectional isolator according to DIN EN 54-7 and EN 54-17. •

  • Suitable for direct use in environments with air flows of 20 m/s
  • Intelligent evaluation to eliminate interference variables
  • Highest operational reliability thanks to intelligent smoke chamber measurement sensors
  • Exact contamination detection through additional, independent measuring section
  • Detector sensitivities can be automatically adjusted and freely programmed
  • Fault monitoring for measuring chamber signal and loop3000 electronics
  • Periodically carrying out a sensor test
  • Automatic and manual addressing on the loop3000
  • Integrated insulator and T-branch
  • Alarm output for controlling a detector parallel display
  • Functionalities fully integrated via loop3000 protocol
  • Presence and absence switching with freely selectable sensitivities
  • Storage of the last maintenance date
  • Mode for learning environmental conditions
  • Illustration of a temperature profile of the fire alarm system
  • Multicolor LED for alarm (red) and fault display (yellow)
  • Delivery includes dust cover for installation phases

TECHNICAL DATA:

Operating voltage: 15 to 34 V DC on 2-wire bus
Quiescent current: 280 µA
Alarm current: 5mA
OC output: Max. 10 mA for parallel display or piezo base
Protection class: IP 40
ambient temperature; -10°C to +60°C
Humidity: Max. 95%
Response sensitivity: adjustable in 5 sensitivity levels
Dimensions: (H x D) 44mm x 100mm
Material: ABS color
Housing: white (similar to RAL 9003)
Standards: 54-5 class A1, 54-7, 54-17
VdS recognition:G 202107
System approval: S 295054, S 208123 and S 210001
CPD number: 0786-CPD-20036