Skip to content

Produktübersicht

Output card for the monitored connection of up to 4 additional short-circuit-proof signaling lines to the fire alarm panels of the detect 3004plus series.

  • Provision of additional 4 monitored and short-circuit-proof outputs, each with a maximum of 580 mA line current
  • Connection option for signal transmitters in the high and low impedance range through an integrated pole switching
  • Possibility of activating the participation of the outputs in the "external signaling devices on/off" function of the fire alarm panel
  • 4 inputs for controlling the signaling lines
  • Setting option for individual or collective control of all signal generator lines via jumpers
  • 24 V power supply via the fire alarm control panel power supply
  • Module housing for easy installation on a top-hat rail
  • 12 LED displays for status and operating states
  • Cascading of several modules of the same type possible
Supply voltage 21V to 37V DC
Quiescent current 90mA
Alarm current 500 to 2600mA
Exit 4 mm x 580 mA monitored, short circuit proof, switchable for high and low resistance applications
Ambient temperature -10°C to +50°C
humidity 10% to 85% (non-condensing)
Dimensions (H x W x D) 125mm x 130mm x 70mm
Weight 220g
material SECTION
Color green