Produktübersicht
Intelligent extinguishing control module for the Loop 3000 with bidirectional isolator for controlling single-area extinguishing systems. With two monitored inputs (resting resistance 3.3 k ohms; triggering 3.3 k ohms || 680 ohms) and a potential-free optical relay output (resting resistance 3.3 k ohms; triggering 3.3 k ohms || 680 ohms). The states are displayed on the display of the dc3500 fire alarm control panel.
- Meets SSL criteria according to VdS 2496 and VdS 2540
- Monitoring of operating states via the Loop 3000
- Automatic and manual addressing on Loop 3000
- Integrated bidirectional isolator
- LED service display for alarm (red), fault display and signs of life (yellow) on the housing
- Weather-resistant, halogen-free and impact-resistant housing according to DIN EN 60670 (VDE 0606)
Technical data:
Supply voltage |
17V to 32V DC (abs. max. 34 V DC) on 2-wire bus |
Quiescent current |
approx. 460 µA |
Alarm current |
6mA |
Exit |
1 optical relay, potential-free |
Ambient temperature |
-20°C to +60°C |
Storage temperature |
-25°C to +85°C |
Protection class |
IP54 |
Dimensions (H x W x D) |
93mm x 93mm x 55mm |
Weight |
115g |
material |
polycarbonate, Membranes made of TPE |
Color |
Gray |
Norms |
EN 54-18:2005, EN 54-17:2005 |
VdS recognition |
G216010 |
CE CPR number |
0786-CPR-21491 |
Remarks |
Per system DC3500 maximum 1 ECM module usable. No operation in Sting approved. |