Produktübersicht
Intelligent mini input/output module for the Loop 3000 for controlling external optical and acoustic signaling devices with bidirectional isolator for integration into external connection modules according to EN 54-18. With a monitored fault input and an open collector output for signaling devices.
- Interface module with a freely programmable input and output
- Integrated automatic reset function of the output when the fire alarm control panel signals “external signaling devices on/off”.
- Monitoring the operating status via the Loop 3000
- Independent programming of input and output
- Automatic and manual addressing on Loop 3000
- Integrated insulator
- Fully encapsulated module for integration into special applications controlled by the Loop 3000
- Functionalities fully integrated via Loop 3000 protocol
- With VdS-compliant installation in the Mini 25L housing (item no. 53372)
Supply voltage |
15 V to 32 V DC (abs. max. 34 V DC) on 2-wire bus |
Quiescent current |
380µA |
Alarm current |
380µA; 5 mA when alarm LED active |
Exit |
Open collector 500 mA, 30 V DC |
Ambient temperature |
-10°C to +60°C |
humidity |
Max. 95% (non-condensing) |
Protection class |
IP30 |
Dimensions (H x W x D) |
27mm x 73mm x 15mm |
Weight |
20g |
material |
SECTION |
Color |
Black housing |
Norms |
54-17, 54-18 |
VdS recognition |
G206047 |
System approval |
S210001 |
CE CPD number |
0786-CPD-20530 |