Skip to content

Produktübersicht

Fire department display panel according to DIN 14662 for conventional and redundant connection to the BMZ dc3500. Initial information means for the fire brigade in accordance with DIN 14675 and EN 54-2
Redundant connection in conjunction with the ADP4000 adapter. A connection to the detect 3004plus is also possible. An additional RS 232 module is required to connect to a detect 3004plus. Connection of the components in a loop structure.

  • Supply voltage and signal path redundant
  • Monitoring for short circuits and interruptions according to EN 54-2
  • Full functionality in the event of a disruption to a line route
  • Graphic display with 6 lines (128 x 64 pixels)
  • Operator/installer logo editable
  • Free slot for additional interface for expansion
  • Energy saving design
  • Reduction of environmental influences through capacitive buttons
  • History function
  • Configuration with the Prog4000 programming tool
  • Front door lock with box lock for profile half cylinder according to DIN 18252
  • Standard version for surface mounting
  • Prepared for assembly and connection to the BMZ dc3500
  • Multiple redundant FAT or ZPA in a System 4000 loop
  • Several "slave" FAT or ZPA on one FAT4000 "stub"
  • Several "slave" FAT or ZPA in total in the system 4000
  • Monitoring of transmission paths according to EN 54-13

Technical data:

Supply voltage 10V to 30V DC
Quiescent current approx. 40 mA/16 mA
(12V/24V)
Alarm current approx. 45 mA/23 mA
(12V/24V)
Dimensions (H x W x D) 185mm x 255mm x
58mm
Color RAL 7032 (pebble gray)
VdS recognition G213058