Skip to content

Produktübersicht

Adapter assembly for installation in the BMZ dc3500 to provide the redundant connection for the FAT4000. It is required for the redundant transmission path in accordance with EN 54-2/DIN 14675 and for connection to the higher-level and lower-level BMZ and networking of new and old systems in accordance with DIN 14675 and VdS 2878. The adapter module is used to connect third-party systems in accordance with DIN 14674 and VDS 3531 using ESPA 4.4.4 and ESPA-X protocol - The adapter module offers additional redundancy to compensate for the failure of software-controlled system components according to EN 54-2 with more than 512 detectors.

  • Supply voltage and signal path redundant
  • Monitoring for short circuits and interruptions according to EN 54-2
  • Monitoring of transmission paths according to EN 54-13
  • Full functionality in the event of a disruption to a line route
  • USB interface for easy and time-saving commissioning of the entire system, troubleshooting and maintenance
  • Free slot for additional interface for expansion
  • 7 diagnostic LEDs for quick status analysis
  • Standard version for DIN rail mounting
  • Prepared for assembly and connection to the BMZ dc3500
  • Multiple redundant FAT or ZPA in a System 4000 loop
  • Several "slave" FAT or ZPA on one FAT4000 "stub"
  • Several "slave" FAT or ZPA in total in the system 4000
  • 1 M4-RS485 module for connection to the BMZ dc3500 included in delivery

Technical data:

Supply voltage 10V to 30V DC
Quiescent current approx. 40mA/30mA
(12V/24V)
Dimensions (H x W x D) 115mm x 25mm x
90mm
VdS recognition G213058
Remarks Power supply of the
Loop devices max. 400 mA