Produktübersicht
Zone module, external power supply, C-NET.
- Connection of a detector line (collective or conventional 110 series, DS11, SynoLINE 300/600).
the C-NET
- LED display of the status of the detector line: fault, test, etc.
- Two-wire installation for all cable types
- DC 24 V external power supply (detector lines galvanically isolated)
- Microprocessor-controlled signal evaluation
- Communication via C-NET (individually addressed)
- Can be used in dry, dusty and damp areas
- Various mounting options
- Group module including 1 20 V voltage reference diode and 2 mounting feet for TS35 top hat rail
Data sheet A6V10402143
Operating temperature -10…+50 °C
Standard EN 54-17, EN 54-18
Relative humidity ≤95% rel.
Protection class IP30
IP65: with additional housing FDCH221
Operating voltage DC 12...33 V
Terminating resistor 20 V transzorb diode or EOL22(Ex)
Storage temperature -30…+70 °C
Cable size 0.2...1.5 mm2
System compatibility C-NET > FS720
C-NET communication protocol
Detector line 110 series / DS11, SynoLINE300/600
Dimensions (W x H x D) 95 x 71 x 23 mm
Color of housing: ~RAL 9010 pure white
Lid: Transparent matt
Input voltage DC 12...33 V
Accessories FDCH221 housing with cover, seal and
screws
A5Q00004478 Metal cable gland M20 x
1.5
A5Q00004479 Metal lock nut M20
DBZ1190-AB connecting terminal 1.0…2.5 mm2
(3 pole)
FDCM291 mounting feet (25 pieces)
You may also like
Siemens FDCIO222 DC module 4-IN/OUT
SiemensFor switching on 4 independent, potential-free work or rest contacts for reporting technical conditions (e.g. door or ventilation control) or for t...
View full detailsSiemens FDCI222 DC module 4-IN
SiemensFor switching on 4 independent, potential-free work or rest contacts to display technical statuses (e.g. door or ventilation control) or to trigger...
View full detailsSiemens FDCI361 input module
SiemensFor switching on 1 potential-free working or normally closed contact for reporting technical conditions (e.g. door or ventilation control) or to ...
View full detailsSiemens FDCI221 input module (1 input)
SiemensInput module (1 input) For switching on 1 potential-free working or normally closed contact for reporting technical conditions (e.g. door or v...
View full detailsSiemens FDCL221-M multiple line separator
SiemensTo ensure that several branch lines do not fail in the event of a short circuit, line separators can be connected between them. The line separator...
View full details