Produktübersicht
Intelligent active laser smoke aspirating detector for the earliest detection of fires in sensitive and heavily polluted environments such as IT areas, operating rooms, storage areas, waste incineration plants, etc. Without display.
- Integrated automatic adaptation of the detector to the ambient conditions via intelligent teach-in modes
- Intelligent laser sensing and inclusion of environmental criteria for rapid detection in difficult environments
- Maximum operational safety through optimal adjustment of alarm thresholds via intelligent algorithms for fire detection
- Verification of dynamic environmental parameters and inclusion in the measurement to avoid false alarms
- Automatic day/night switching for optimal adaptation of the smoke extraction system to environmental conditions that vary over time
- Integrated procedure for automatic configuration of the system
- Special integrated technology to avoid influences caused by pollution (dust etc.)
- Integrated dust filter
- Can be equipped with up to 4 intake pipes
- Total pipe length max. 200 m; Max. length of a pipe: 100 m
- Max. number of holes according to EN 54-20 Class C: 80, Class B: 60, Class A: 20
- 1 return pipe to compensate for system-internal pressure differences
- Integrated RS485 interface for networking up to 127 system participants
- Integrated potential-free relay outputs for alarm and faults
- External power supply required
- Connection to the Loop 3000 via IOM 3311
Technical data:
Supply voltage |
21.6V to 26.4V DC external |
Exit |
5 potential-free relay for information, Pre-alarm, fire 1, Fire 2, malfunction |
Ambient temperature |
-10°C to +60°C |
humidity |
max. 90% non-cond. |
Protection class |
IP50 |
Dimensions (H x W x D) |
372mm x 427mm x 95mm |
Weight |
5.2kg |
material |
Cast aluminum, ABS |
Color |
Housing light gray |
Norms |
54-13 |
VdS recognition |
G203024 |
System approval |
S 210001, S 216001 |
further approvals |
LPCB, CCC |
Remarks |
Software for the Interpretation attached Manufacturer Kidde Products Ltd. |
Responsiveness |
adjustable from 0.002 up to 25% obs/m |
Current consumption |
450 mA at 24 V DC |
Particle sensitivity |
0.0003 µm to 10 µm |
Pipe diameter |
3/4" |